赫斯曼现场总线收发器OZD Profi 12M G12 PRO
产品简介
详细信息
Product description
Type: | OZD Profi 12M G12 PRO |
Name: | OZD Profi 12M G12 PRO |
Description: | Interface converter electrical/optical for PROFIBUS-field bus networks; repeater function; for plastic FO; short-haul version |
Part Number: | 943 905-321 |
Port type and quantity: | 2 x optical: 4 sockets BFOC 2.5 (STR); 1 x electrical: Sub-D 9-pin, female, pin assignment according to EN 50170 part 1 |
More Interfaces
Power Supply: | 5-pin terminal block, screw mounting |
Signaling contact: | 5-pin terminal block, screw mounting |
Network size - length of cable
Multimode fiber (MM) 50/125 µm: | 3000 m, 13 dB link budget at 860 nm; A = 3 dB/km |
Multimode fiber (MM) 62.5/125 µm: | 3000 m, 15 dB link budget at 860 nm; A = 3.5 dB/km |
Multimode fiber HCS (MM) 200/230 µm: | 1000 m 18 dB link budget at 860 nm; A = 8 dB/km, 3 dB reserve |
Power requirements
Current consumption: | max. 200 mA |
Input voltage range: | -7 V ... +12 V |
Operating Voltage: | 18 ... 32 VDC, typ. 24 VDC |
Power consumption: | 4.8 W |
Redundancy functions: | HIPER-Ring (ring structure), redundant 24 V infeed |
Power Output
Output voltage/output current (pin6): | 5 VDC +5%, -10%, short circuit-proof/90 mA |
Ambient conditions
Operating temperature: | 0-+60 °C |
Storage/transport temperature: | -40-+70 °C |
Relative humidity (non-condensing): | 10-95 % |
Mechanical construction
Dimensions (WxHxD): | 35 x 156 x 119 mm |
Weight: | 200 g |
Housing Material: | plastics |
Mounting: | DIN rail |
Protection class: | IP20 |
Approvals
Basis Standard: | EU Conformity, AUS Conformity Australia |
Safety of information technology equipment: | cUL508 |
Hazardous locations: | ISA 12.12.01 Class 1 Div. 2 |
ATEX Zone 2 |
Scope of delivery and accessories
Scope of delivery: | device, start-up instructions |