旁路电压容限
+/-10% settable from +/-4/6/8 and 10%
额定输出电压
400V 3PH, 480V 3PH
输出频率(与主频率同步)
50 Hz, 60 Hz
输出连接
(1) Hard Wire 4-wire (3PH + G) | |
(1) Hard Wire 5-wire (3PH + N + G) | |
输出电压容差
+/-1% static and +/- 5% at 99% load step
输出电压 THD
< 2% linear load and <3% non-linear load
过载工作
10 minutes @ 125% and 60 seconds @ 150%
额定输入电压
400V 3PH, 480V 3PH
输入端子类型
Hard Wire 4-wire (3PH + G) | |
Hard Wire 5-wire (3PH + N + G) | |
工作电压范围
340 - 460 (400V), 408 - 552 (480)V
输入总谐波失真
Less than 5% for full load
过载工作
10 minutes @ 125% and 60 seconds @ 150%
可选用电池
APC Symmetra PX 150kW Scalable to 250kW with Right Mounted Maintenance Bypass and Distribution
Curve | Part Number(s) |
A | SY150K250DR-PD |
B | SY150K250DR-PD + (3)SYBT9-B6 |
C | SY150K250DR-PD + (6)SYBT9-B6 |
D | SY150K250DR-PD + (1)SYBFXR8-8 |
E | SY150K250DR-PD + (2)SYBFXR8-8 |
曲线拟合测得的运行时间数据。 所有测量都是在使用充满电的新电池、在典型环境条件下且没有电力输入和电阻负载输出的情况下开展的。
Load | Efficiency |
25% | 95.0% |
50% | 96.1% |
75% | 96.3% |
99% | 96.2% |
浏览上面的“能源利用率”图表线来查看
的效率与负载比详情 根据针对不间断电源(UPS)的能源之星计划要求产品规范对所测数据进行曲线拟合- 适用性标准版本1.0。所有测量数据取自正常模式,在典型环境条件下使用480V/60Hz电压输入和平衡电阻负载(PF = 1.0)输出。
听觉噪音距设备表面 1 m 处
54.00 dBA
管理机构认证
cUL Listed, CE标志, CSA C22.2 07.3-05, EN/IEC 62040-1-1, EN/IEC 62040-2, EN/IEC 62040-3, 能源之星 (美国), Eurobat通用型, OSHPD, UL 1778, UL 60950-1
标准质保
厂家的启动装置提供 1 年现场保修或保换
**UPS带50%额定容量负载放电至关机后,重新充电到90%电池容量所需时间 。