产品简介

西门子模拟量模块 6ES73317NF000AB0 SIMATIC S7-300, 逻辑输入 SM 331, 光隔离, 8 AE; +/-5/10V, 1-5 V, +/-20MA, 0/4 TO 20MA, 16 BIT (55 MS), 1 COMMON POINT(50 V COM.), 1 X 40 针

详细介绍

概述

应用

模拟量输入模板用来实现PLC与模拟量过程信号的连接。用于连接电压和电流传感器、热电耦、电阻和热电阻

功能

模拟量输入模块将来自过程的的模拟量信号转换为可在控制器中进行内部处理的数字量信号。

该模块具有如下特点:

6ES7331-7KF02-0AB0  SM331, 8AI, 9/12/14BIT

6ES7331-7HF01-0AB0  SIMATIC S7-300, ANALOG INPUT

6ES7331-1KF02-0AB0  SM331, 8AI, 13BIT

6ES7331-7KB02-0AB0  SM331, 2AI, 9/12/14BIT

6ES7331-7PF01-0AB0  SIMATIC S7-300, ANALOG INPUT

6ES7331-7PF11-0AB0  SIMATIC S7-300, ANALOG INPUT

6ES7331-7PE10-0AB0  SM331, 6AI, 16BIT, THERMOCOUPLE

6ES7331-7NF00-0AB0  SIMATIC S7-300, ANALOG INPUT

6ES7331-7NF10-0AB0  SIMATIC S7-300, ANALOG INPUT

SM 332 模拟量输出模块

概述

应用

模拟量输出模块用于从PLC向过程变量输出模拟量信号。适用于连接模拟量执行器。

功能

模拟量输出模块将控制器的数字信号转换成过程所需的模拟量信号(电流或电压)。

该模块具有如下特点:

6ES7332-5HB01-0AB0  SIMATIC S7-300, ANALOG OUTPUT

6ES7332-5HD01-0AB0  SIMATIC S7-300, ANALOG OUTPUT

6ES7332-5HF00-0AB0  SIMATIC S7-300, ANALOG OUTPUT

6ES7332-7ND02-0AB0  SIMATIC S7,SM 332 ANALOG OUTPUT

 

SM 334 模拟量输入/输出模块

概述

应用

模拟量输入/输出模块适用于连接模拟传感器和执行器。

设计

模拟量输入/输出模块的特性:

功能

模拟量输入/输出模块转换:

功能如下:

技术规范

Article number

6ES7334-0CE01-0AA0

6ES7334-0KE00-0AB0

 

SIMATIC S7, ANALOG INPUT MODULE

SIMATIC S7-300, ANALOG MODULE

Supply voltage

  

Load voltage L+

  
  • ● Rated value (DC)

24 V

24 V

  • ● Reverse polarity protection

 

Yes

Input current

  

from supply and load voltage L+ (without load), max.

110 mA

80 mA

from backplane bus 5 V DC, max.

55 mA

60 mA

Power loss

  

Power loss, typ.

3 W

2 W

Analog inputs

  

Number of analog inputs

4

4

  • ● For voltage measurement

4

2

  • ● For resistance measurement

 

4

permissible input voltage for voltage input (destruction limit), max.

20 V

20 V; continuous; 75 V for max. 1 s (mark to space ratio 1:20)

permissible input current for current input (destruction limit), max.

40 mA

 

Cycle time (all channels) max.

5 ms

85 ms

Input ranges

  
  • ● Voltage

Yes

Yes

  • ● Current

Yes

No

  • ● Thermocouple

No

No

  • ● Resistance thermometer

No

Yes

  • ● Resistance

No

Yes

Input ranges (rated values), voltages

  
  • ● 0 to +10 V

Yes

Yes

  • ● Input resistance (0 to 10 V)

100 kΩ

100 kΩ

Input ranges (rated values), currents

  
  • ● 0 to 20 mA

Yes

 
  • ● Input resistance (0 to 20 mA)

50 Ω

 

Input ranges (rated values), resistance thermometer

  
  • ● Pt 100

 

Yes; only climatic range

Input ranges (rated values), resistors

  
  • ● 0 to 10000 ohms

 

Yes

Analog outputs

  

Number of analog outputs

2

2

Voltage output, short-circuit protection

Yes

Yes

Voltage output, short-circuit current, max.

11 mA

30 mA

Current output, no-load voltage, max.

15 V

 

Output ranges, voltage

  
  • ● 0 to 10 V

Yes

Yes

Output ranges, current

  
  • ● 0 to 20 mA

Yes

 

Load impedance (in rated range of output)

  
  • ● with voltage outputs, min.

5 kΩ

2.5 kΩ

  • ● with voltage outputs, capacitive load, max.

1 µF

1 µF

  • ● with current outputs, max.

300 Ω

 
  • ● with current outputs, inductive load, max.

1 mH

 

Cable length

  
  • ● shielded, max.

200 m

100 m

Analog value generation for the inputs

  

Integration and conversion time/resolution per channel

  
  • ● Resolution with overrange (bit including sign), max.

8 bit

12 bit

  • ● Integration time (ms)

 

16,67 / 20 ms

Analog value generation for the outputs

  

Integration and conversion time/resolution per channel

  
  • ● Resolution with overrange (bit including sign), max.

8 bit

12 bit

Settling time

  
  • ● for resistive load

0.3 ms

0.8 ms

  • ● for capacitive load

3 ms

0.8 ms

  • ● for inductive load

0.3 ms

 

Encoder

  

Connection of signal encoders

  
  • ● for current measurement as 2-wire transducer

No

 
  • ● for current measurement as 4-wire transducer

Yes

 
  • ● for resistance measurement with two-wire connection

 

Yes

  • ● for resistance measurement with three-wire connection

 

Yes

  • ● for resistance measurement with four-wire connection

 

Yes

Errors/accuracies

  

Operational error limit in overall temperature range

  
  • ● Voltage, relative to input range, (+/-)

0.9 %

0.7 %; 0 to 10V

  • ● Current, relative to input range, (+/-)

0.8 %

 
  • ● Resistance, relative to input range, (+/-)

 

3.5 %; 10 kOhm

  • ● Resistance thermometer, relative to input range, (+/-)

 

1 %

  • ● Voltage, relative to output range, (+/-)

0.6 %

1 %

  • ● Current, relative to output range, (+/-)

1 %

 

Basic error limit (operational limit at 25 °C)

  
  • ● Voltage, relative to input range, (+/-)

0.7 %

0.5 %; 0 to 10V

  • ● Current, relative to input range, (+/-)

0.6 %

 
  • ● Resistance, relative to input range, (+/-)

 

2.8 %; 10 kOhm

  • ● Resistance thermometer, relative to input range, (+/-)

 

0.8 %

  • ● Voltage, relative to output range, (+/-)

0.5 %

0.85 %

  • ● Current, relative to output range, (+/-)

0.5 %

 

Interrupts/diagnostics/status information

  

Alarms

No

No

Diagnostic functions

No

No

Potential separation

  

Potential separation analog inputs

  
  • ● between the channels and backplane bus

No

Yes

Potential separation analog outputs

  
  • ● between the channels and backplane bus

No

Yes

Isolation

  

Isolation tested with

500 V DC

500 V DC

Connection method

  

required front connector

20-pin

20-pin

Dimensions

  

Width

40 mm

40 mm

Height

125 mm

125 mm

Depth

117 mm

117 mm

Weights

  

Weight, approx.

285 g

200 g